Self-test

Eneru handles UPS battery self-tests two ways:

  1. Observe the result of a test the UPS ran on its own — on the device's own schedule or triggered by hand — and record it (no configuration required).
  2. Issue a test itself — on a schedule, from the CLI, or from the dashboard.

Both feed the battery-health score. Issuing uses the same NUT upscmd path as UPS control.

Observing device-run tests (no config)

On every poll Eneru reads ups.test.result / ups.test.date and, when a new settled result appears (passed, warning, failed, or aborted), records it as a source: device row. This happens whether or not scheduled self-tests are enabled — many UPSes run a test on their own cadence (ups.test.interval), and some operators only ever test by hand. The latest result shows up in the dashboard, the API selfTest block, the Prometheus series, and the battery-health score with no setup.

Issuing tests: safety model

Issuing a test is a write surface, so it always requires API authentication — an explicit api.auth.enabled: true, or simply a user in the auth DB (eneru user create), which activates auth with no restart. Auth-off always means read-only.

Enabling self_test is its own narrow permission: it grants exactly the one command in self_test.command. You do not also need nut_control.enabled or that command on nut_control.allowed_commands — the general control surface (arbitrary /command, variable writes) stays gated separately. Credentials for upscmd still come from nut_control.username/password when your upsd requires a login to run instant commands.

If upscmd -l does not expose the configured command, the feature self-disables for that UPS with a logged warning. Note that some upsd setups (notably UniFi's NUT) only return the command list to a logged-in client — Eneru forwards the nut_control credentials to upscmd -l so discovery works there.

The command name varies by vendor. The test.battery.start default is not universal: APC devices via the usbhid-ups driver expose test.battery.start.quick and test.battery.start.deep (plus test.battery.stop) but not the bare test.battery.start. When the configured command isn't offered, the CLI and the API's 422 response now list the battery-test commands the UPS does expose, so you can set self_test.command to the right one. Run upscmd -l <ups> yourself to see the full list.

Multi-UPS: the self-test command is per-UPS. When UPSes live on different upsd servers, set self_test.command (and, if that upsd needs a login, nut_control.username / password) under each ups: list entry — see the multi-UPS example in examples/config-reference.yaml.

Configuration

api:
  auth:
    enabled: true            # or just: eneru user create <name>

self_test:
  enabled: true
  schedule: monthly          # daily | weekly | monthly | "every <N>d|h|m"
  time: "03:00"              # wall-clock for calendar schedules
  command: test.battery.start # adapts to what upscmd -l exposes
  result_poll_after: 60      # seconds to wait before reading the result

# Only needed if your upsd requires a login for upscmd (list/issue). The
# self_test command above is auto-permitted; you do NOT need nut_control.enabled
# or an allowed_commands entry just for self-test.
nut_control:
  username: "eneru"
  password: "secret"

schedule accepts daily, weekly, monthly, or an interval such as every 30d / every 12h. The scheduler persists its last-run time, so a 30-day cadence survives daemon restarts (it does not reset to "now" on boot), and a restart never kicks off an unscheduled test. self_test is a SAFE hot-reload section: its Schedule is recomputed from config on every loop, so a SIGHUP schedule change is picked up on the next due-check with no re-register step.

Result normalization

The raw ups.test.result string is vendor-specific and unbounded, so Eneru stores it verbatim and maps it to a small stable enum that the API, Prometheus, and UI consume:

passed · warning · failed · aborted · running · unknown · unsupported

Eneru writes the active test row before it sends the NUT command. Think of the row as a claim ticket: if the daemon restarts after issuing the command, it can still find the ticket and finish tracking the result. A second test is refused while that ticket is active. If the row cannot be stored, Eneru sends no command.

After result_poll_after, Eneru reads the result. running and unknown are polled again at the same interval instead of being treated as final. Polling ends on a terminal result or after 24 hours; a timeout becomes unknown. Eneru queues one start notification and one terminal notification per test, including across daemon restarts.

The direct CLI path has no resident monitor. Its active ticket therefore blocks another direct test for at most 24 hours; after that, the stale row becomes unknown and a new test may start.

Power events and failed tests

A UPS may briefly report OB while it exercises the battery. If Eneru sees CAL, a running result, or a recently issued test, it records that pair as SELF_TEST_ON_BATTERY and SELF_TEST_POWER_RESTORED. Ordinary outage notifications are suppressed for the pair, but FSD, low battery, runtime, depletion, extended-time, and connection-loss protections still run. If the UPS remains on battery after the test finishes, Eneru records a normal ON_BATTERY event and treats the continuing interval as a utility outage.

A hard failed result persists a failure latch. A later passed result clears it; warning, aborted, and unknown leave it unchanged. The failed test does not shut anything down while line power is present or during the test's own OB interval. On a later genuine outage, shutdown starts after triggers.self_test_failure_shutdown_delay, which defaults to 30 seconds. Set the value to 0 to act on the first poll of that later outage.

Redundancy members publish this condition as an advisory trigger and let the group quorum decide whether to act. A monitoring-only UPS sends a critical notification but runs no shutdown actions.

CLI

# Issue a test through the running daemon (the daemon owns the audit record and
# the self_tests row in its state DB). Needs an API credential:
eneru self-test run --token "$ENERU_TOKEN"            # or --api-key / $ENERU_API_TOKEN
eneru self-test run --ups "UPS-B@10.0.0.11" --url http://127.0.0.1:9191

# Or issue directly via NUT with no daemon (one-shot; still allowlist-checked):
eneru self-test run --direct --config /etc/ups-monitor/config.yaml

# Read the latest recorded result (from the local stats DB):
eneru self-test status

run defaults to the API client so a single daemon owns the issue, audit, and recording. --direct issues test.battery.start straight through nut_control credentials and records the row in the configured stats DB — use it when no daemon is running. --ups defaults to the only configured UPS.

API and dashboard

  • POST /api/v1/ups/{name}/self-test — auth-gated and audited. Permitted when self_test is enabled (grants exactly self_test.command) or the general nut_control surface allows the command.
  • The latest result appears in the selfTest block of GET /api/v1/ups, including its source (device for an observed test, scheduler/api/cli for one Eneru issued). (The GET /api/v1/ups/{name}/battery-health endpoint returns the health score and replacement projection; the self-test result lives in the status selfTest block.)
  • The dashboard Control tab has a per-UPS Run self-test button; the Battery tab shows the latest result.
  • Prometheuseneru_ups_self_test_result{result="passed|failed|..."} (the normalized enum, never the raw vendor string as a label).

Testing it for real

The NUT dummy driver has no INSTCMD, so issuing a test has no end-to-end CI coverage (the issue logic is unit-tested). The observe path is covered end-to-end: the E2E suite serves passive running and failed states, checks self-test attribution, then simulates an unknown-status interval followed by a later outage and verifies the delayed failed-test trigger without an OL poll. On real hardware, confirm upscmd -l lists your test command first — e.g. the Ubiquiti TOWER_1000VA exposes test.battery.start (pass nut_control credentials if your upsd requires a login to list) — then run eneru self-test run and check eneru self-test status.