Redundancy groups

A redundancy group protects one set of resources with two or more UPS sources. Eneru shuts the group down only when the configured quorum is lost.

Use this for dual-PSU servers, A+B rack feeds, and other setups where losing one UPS does not mean the protected system has lost power.

When to use one

Situation Use a redundancy group?
One UPS feeds one server No. Use a normal UPS group
Two UPSes feed two independent racks No. Use multi-UPS groups
Two UPSes feed both PSUs on the same server Yes
Two UPSes feed a shared A+B rack Yes

The practical test is simple: if a resource can survive one UPS failure, put it in a redundancy group instead of assigning it directly to a single UPS group.

Example

ups:
  - name: "UPS-A@10.0.0.10"
  - name: "UPS-B@10.0.0.11"

redundancy_groups:
  - name: "rack-1-dual-psu"
    ups_sources:
      - "UPS-A@10.0.0.10"
      - "UPS-B@10.0.0.11"
    min_healthy: 1
    degraded_counts_as: healthy
    unknown_counts_as: critical
    remote_servers:
      - name: "Compute Node 1"
        enabled: true
        host: "10.0.0.20"
        user: "root"

With two UPSes and min_healthy: 1, the group tolerates one failed UPS. It shuts down only when the healthy count drops below 1.

Fields

Key Default Description
name required Unique group label
ups_sources required Two or more UPS names from the top-level ups: list
min_healthy 1 Shutdown fires when healthy member count is below this number
degraded_counts_as healthy Count DEGRADED members as healthy or critical
unknown_counts_as critical Count UNKNOWN members as critical, degraded, or healthy
is_local false This group powers the Eneru host and may own local resources
triggers inherits Trigger overrides for this group
remote_servers [] Remote resources owned by the group
virtual_machines, containers, filesystems disabled Local resources. Valid only when is_local: true

Quorum

The group fires when:

healthy_count < min_healthy

For a two-UPS dual-PSU server:

min_healthy Behavior
1 Shut down when both UPSes fail. This is the usual choice
2 Shut down when either UPS fails. This removes practical redundancy

For a three-UPS group:

min_healthy Behavior
1 Tolerate two failed members
2 Tolerate one failed member
3 Shut down when any member fails

min_healthy: 0 is invalid because the group would never shut down.

Member states

Each UPS member is classified on every evaluator tick.

State Meaning
HEALTHY UPS reports usable data and no active problem
DEGRADED UPS is visible but in a warning state, such as on battery or voltage warning
CRITICAL UPS hit a shutdown trigger, FSD, overload-critical path, or explicit advisory condition
UNKNOWN Snapshot is stale, NUT connection is lost, or the monitor cannot provide current data

degraded_counts_as controls whether warning states still contribute to quorum. unknown_counts_as controls how missing data is counted. The default is tolerant of degraded power but fail-safe on missing visibility.

Advisory triggers

Member UPS triggers still run. In a redundancy group they do not directly run the shutdown sequence. They mark the member as advisory-critical, then the group evaluator decides whether quorum is gone.

Group-level triggers: are also evaluated by the redundancy evaluator itself. Use them when a shared resource has a different risk budget than the member UPS defaults; the group trigger can mark that member critical for quorum without changing the UPS monitor's own config.

depletion.critical_rate and depletion.grace_period can be group-local. depletion.window cannot: the rolling depletion rate is calculated by each UPS monitor before the redundancy evaluator sees the snapshot. Configure depletion.window globally or on ups[*].triggers instead.

You will see log lines like:

Trigger condition met (advisory, redundancy group): battery below threshold

For min_healthy: 1, that advisory condition only shuts down the protected resource if every other member has also stopped counting as healthy.

Local ownership

At most one group across the whole config can be is_local: true. That group may own local VMs, containers, filesystems, and local shutdown behavior.

This is valid:

redundancy_groups:
  - name: "local-dual-feed"
    is_local: true
    virtual_machines:
      enabled: true

This is not valid if another UPS group already has is_local: true.

Remote-server ownership

A remote server, identified by host and user, can belong to only one place:

  • One UPS group's remote_servers list.
  • One redundancy group's remote_servers list.

Validation rejects duplicate ownership so Eneru cannot shut down the same server through two paths.

Validate

sudo eneru validate --config /etc/ups-monitor/config.yaml

Validation prints configured redundancy groups:

Redundancy groups (1):
  1. rack-1-dual-psu
     Sources (2): UPS-A@10.0.0.10, UPS-B@10.0.0.11
     Quorum: min_healthy=1 (degraded->healthy, unknown->critical)
     Remote servers (1): Compute Node 1

Common validation failures:

Error class Cause
Unknown UPS source ups_sources does not exactly match a top-level ups[].name
Duplicate UPS source Same member listed twice
Duplicate group name Two redundancy groups share a name
Multiple local groups More than one UPS or redundancy group has is_local: true
Duplicate remote ownership Same host and user assigned to more than one group

Failure timeline

For a dual-UPS group with min_healthy: 1 and default counting:

Time Event Group result
0s UPS-A loses input power UPS-A is DEGRADED, UPS-B is HEALTHY. Quorum holds
60s UPS-A hits low battery UPS-A is CRITICAL, UPS-B is HEALTHY. Quorum still holds
90s UPS-B also loses input power UPS-B is DEGRADED and counts as healthy by default. Quorum holds
120s UPS-B hits low battery Both members are CRITICAL. Quorum is lost and shutdown starts

If you want the group to shut down as soon as a member is merely degraded, set degraded_counts_as: critical.

Sizing warning

Redundancy only works if the remaining feed can carry the load. For A+B power, verify that each UPS can carry the full protected load during single-feed operation.

Good targets:

  • Normal operation: each UPS at or below about 50% load.
  • Single-feed degraded operation: surviving UPS below about 80% load.
  • Extra headroom for inrush, battery age, and generator transitions.

If the surviving UPS overloads, software cannot save the rack. Fix the load or UPS sizing.

Operational notes

Re-entry guard / flag-file lifecycle

Each redundancy group has a flag at /var/run/ups-shutdown-redundancy-{group} that prevents a single quorum-loss event from firing the shutdown sequence twice. From 5.3.0 onward the daemon owns this flag's lifecycle:

  • Cleared at coordinator startup so a stale flag from a prior daemon instance can't silently block the next quorum loss. This is the load-bearing guarantee; the next two clears are optimizations. From 5.3.0-rc4 onward the flag records the owning PID plus Linux process start identity when available, and startup refuses to clear it if that same process is still running. That prevents two overlapping daemon instances from erasing each other's in-flight guard without confusing a stale flag with a reused PID.
  • Cleared on quorum recovery so the next quorum loss can fire its own shutdown without waiting for a daemon restart. Look for quorum restored -- re-armed for next event in the log.
  • Cleared on graceful exit via SIGINT / SIGTERM so the next start is clean. A non-graceful exit (crash, SIGKILL, OOM) leaves the flag on disk, but the next coordinator startup re-clears it.

The flag's only role is in-flight re-entry protection within a single quorum-loss event. It never persists across runs or across events. If the flag cannot be inspected or removed at startup, Eneru treats that as fatal and exits rather than starting with an unreliable shutdown guard.

If the daemon ever sees the flag at first call (someone touched it manually, /var/run is read-only, the startup-cleanup hook was bypassed) it logs the exact line below — operators can grep their journal for it verbatim:

⚠️  Redundancy shutdown for '{group}' suppressed: flag /var/run/ups-shutdown-redundancy-{group} already present at first call (startup cleanup bypassed). Will re-arm when quorum recovers.

Pre-5.3.0 the suppression was silent and cost some operators (issue #4) hours of debugging. If you see the warning, check for stuck SSH sessions, stale lock files, or a previous instance that didn't exit cleanly.

Troubleshooting

Symptom Likely cause
One UPS failed but nothing shut down Quorum still holds. Check min_healthy and member states
On-battery member still counts healthy degraded_counts_as: healthy is the default
Advisory log appears but no shutdown Another member still satisfies quorum
Group never starts ups_sources names do not match exactly
Repeated tests do not fire Pre-5.3.0 only: stale /var/run/ups-shutdown-redundancy-* from a prior run. 5.3.0+ clears these automatically at startup
⚠️ Redundancy shutdown … suppressed log line The startup-cleanup contract was bypassed — see Operational notes above